NSN 5925-01-517-7229

Part Details | CIRCUIT BREAKER

5925-01-517-7229 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Alternate Parts: IEG6IREC46115.021V, IEG6-IREC4-61-15.0-21-V, AM344, AM-344, 5925-01-517-7229, 01-517-7229, 5925015177229, 015177229

Supply Group (FSG) NSN Assigned NIIN Item Name Code (INC)
59FEB 18, 200401-517-722900136 ( CIRCUIT BREAKER )
REFERENCE DRAWINGS & PICTURES

SINGLE POLE TYPE

Cross Reference | NSN 5925-01-517-7229
Part Number Cage Code Manufacturer
IEG6-IREC4-61-15.0-21-V81541SENSATA TECHNOLOGIES MARYLAND, INC
AM-34481541SENSATA TECHNOLOGIES MARYLAND, INC
Technical Data | NSN 5925-01-517-7229
Characteristic Specifications
POLE QUANTITY1
BODY STYLE SINGLE POLE TYPE
BODY LENGTH2.000 INCHES NOMINAL
BODY WIDTH0.750 INCHES NOMINAL
BODY HEIGHT2.075 INCHES NOMINAL
BOSS HEIGHT0.240 INCHES NOMINAL
SPECIAL FEATURESOPERATES IN M40.0-85.0 DEG C; INSULATION RESISTANCE NOT LESS THAN 100 MEGOHMS AT 500 VOLTS DC; DIELECTRIC STRENGTH WITHSTANDS 3750 VAC, 60 HZ FOR 60 SECONDS BETWEEN ALL ELECTRICITY ISOLATED TERMINALS, EXCEPT AUXILIARY SWITCH TERMINSAL SHALL WITHSTAND 600 VAC, 60 HZ FOR REG AND REC TYPES; OPERATING AS A SWITCH THE OPERATING LIFE EXCEEDS 10,000 OPERATIONS AT A RATE OF 6 PER MINUTE WHEN TESTED AS FOLLOWS 6000 OPS AT RATED CURRENT PLUS 4000 OPS AT NO LOAD; ELECTRICAL CHARACTERISTICS 0.050-50 AMPERES; 80VDC MAX, 240VAC MAX, 50/60 HZ AND 0.050-30 AMPERES; 250VAC MAX, 400 HZ; ONE TOGGLE HANDLE PER UNIT; HANDLE COLOR RED
TEST DATA DOCUMENTMIL-STD-202 STANDARD (INCLUDES INDUSTRY OR ASSOCIATION STANDARDS, INDIVIDUAL MANUFACTUREER STANDARDS, ETC.).
SUPPLEMENTARY FEATURESPCT OVERLOAD-TRIP TIME IN SECONDS 100 PCT NO TRIP, 125 PCT 0.7-12, 150 PCT 0.35-7, 200 PCT 0.130-3, 400 PCT 0.030-1, 600 PCT 0.015-0.3, 800 PCT 0.01-0.15, 1000 PCT 0.008-0.1