NSN 5925-01-552-9336
Part Details | CIRCUIT BREAKER
5925-01-552-9336 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
Alternate Parts: JGE3125FAGF02, 5925-01-552-9336, 01-552-9336, 5925015529336, 015529336
| Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 59 | JUN 28, 2007 | 01-552-9336 | 00136 ( CIRCUIT BREAKER ) |
REFERENCE DRAWINGS & PICTURES
MULTIPOLE-SINGLE ACTUATOR TYPE
Cross Reference | NSN 5925-01-552-9336
| Part Number | Cage Code | Manufacturer |
|---|---|---|
| JGE3125FAGF02 | 55588 | EATON ELECTRICAL INC.DBA CUTTLER HMMER CMRCL CNTRLS DIV |
Technical Data | NSN 5925-01-552-9336
| Characteristic | Specifications |
|---|---|
| POLE QUANTITY | 3 |
| RESET METHOD | MANUAL |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| CASE MATERIAL | PLASTIC |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BODY WIDTH | 4.130 INCHES NOMINAL |
| BODY HEIGHT | 3.440 INCHES NOMINAL |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| SPECIAL FEATURES | DC RATINGS ARE OF 2-POLES OF 3-POLE CIRCUIT; TRIP UNIT - FIXED THERMAL AND ADJUSTABLE MAGNETIC; RATED ULTIMATE BREAKING CAPACITIES - 65000.0 AMPS AT 220.0 TO 240.0 VOLTS AC; 25000.0 AMPS AT 380.0 TO 415.0 VOLTS AC; 25000.0 AMPS AT 480.0 VOLTS AC; 18000.0 AMPS AT 600.0 VOLTS AC; 12000.0 AMPS AT690.0VOLTS AC; 10000.0 AMPS AT 250.0 VOLTS DC; OVERALL HEIGHT 7.000 INCHES NOMINAL; FREEZE TESTED (F02) USING SPECIAL LUBRICATION, MECHANICAL OPERATION VERIFIED TO MINUS 40.0 DEGREES C. |